1.Parameter table
Category | Parameter |
Model | GM200/50 |
Capacity | 100kVA |
Main Input | Input Mode: 3P+N+PE Input Voltage: 380/400/415VAC (line voltage); 50/60Hz Power Factor: >0.99 Current Distortion: THDi < 3% (100% linear load) Voltage Range: 304 - 478VAC (line voltage, full load), 304 - 228VAC (line voltage, load derates linearly from 100% to 40%) Frequency Range: 40 - 70Hz |
Battery | Battery Voltage: ±240VDC (32 - 44 cells adjustable) Charging Power: 20% of active power Charging Voltage: ±1% |
Bypass | Rated Voltage: 380/400/415VAC (line voltage); 220/230/240VAC (phase voltage) Voltage Range: Adjustable, default - 20% - +15%; upper limit: +10%, +15%, +20%, +25%; lower limit: - 10%, - 15%, - 20%, - 30%, - 40% Overload Capacity: 110% long - term operation; 110% < load ≤ 125%, not less than 1 minute; 125% < load ≤ 150%, not less than 1 minute; 150% < load, 1s |
Output | Rated Output: 380/400/415VAC (line voltage); 220/230/240VAC (phase voltage) Rated Frequency: 50/60Hz Output Power: 1 Voltage Precision: ±1.0% Output Dynamic: <5% (20% - 80% - 20% step load) Dynamic Recovery: <20ms (0% - 100% - 0% step load) Total Harmonic Distortion (THDu): <1% (linear load), <5% (non - linear load) Inverter Overload: 110% transfers to bypass after 1 hour; 125% after 10 minutes; 150% after 1 minute; >150% after 200ms Frequency Precision: 0.10% Tracking Range: Adjustable, ±0.5Hz - ±5Hz, default ±3Hz Tracking Rate: Adjustable, 0.5Hz/S - 3Hz/S, default 0.5Hz/S Crest Factor: 3:1 Three - phase Phase: 120° ± 0.5° |
System | System Efficiency: Main mode ≥97%; Battery mode ≥97% Display: LCD + LED + color touchscreen (below 300 is 7 - inch, 300 and above is 10 - inch) Safety: IEC62040 - 1, IEC60950 - 1 EMC: IEC62040 - 2; IEC61000 - 4 - 2(ESD); IEC61000 - 4 - 3(RS); IEC61000 - 4 - 4(EFT); IEC61000 - 4 - 5(Surge) Protection Level: IP20 Standard Configuration: USB, RS232, RS485, dry contact, battery cold start, dust screen Optional Accessories: SNMP card, AS400 card, paralleling components, lightning protection components, LBS Working Environment: 0 - 40°C (working temperature); - 25 - 70°C (storage temperature); 0 - 95% (non - condensing) Noise (dB): 72dB @ 100% load, 68dB @ 45% load Altitude: <1000m, between 1000 - 2000m, power derates 1% for every 100m increase |
Dimensions (W*D*H, mm) | 600*1000*1600 |
Weight (kg) (including modules) | 330 (4 - module cabinet) |
2.Qualification Certificates
The company holds the Enterprise Credit Rating Certificate (AAA level), REACH certification report, Rohs certification, laboratory Capability Evaluation Certificate, ISO three-system certification +ISO energy Certification, CE certification, China Energy-saving Product Certification Certificate, EMC electromagnetic compatibility test report, carbon footprint certificate report, CCC compulsory certification, CQC energy-saving certification, etc.3.Packaging and Transportation
Fixed transportation4.Company UPS Cases:
1. Communication operator:5.Company Profile
The company was established in 2012 and is a professional manufacturer specializing in full-network energy solutions for critical infrastructure in the data center and industrial sectors. The company adheres to the development concept of "not fearing change and embarking on a new journey of its own", and is committed to the research and development, production and sales of products in the field of energy conservation for data centers. In 2018, the company passed the ISO certification. In 2019, it fully entered the field of data center cooling product complete machine solution contract manufacturing. In 2022, it registered the new technical brand "Weishan" and established an after-sales service system. From 2023 to 2024, the company's products were launched and recognized by customers, and a national sales team was established.